HomeSizerSizing worksheets for US homes

Index / Power / Sheet 06

Sheet 06 · Power

Generator Size Calculator (Watts)

Last updated Planning estimate

Enter how many of each item you want running at the same time. The sheet adds the running watts, then adds the single largest starting surge. Generac and Briggs & Stratton both size this way.

Worksheet

Estimate only: This is a planning estimate. Equipment selection, installation and any permit work should be confirmed with the manufacturer's specifications, your local authority, or a licensed professional.

How it works

Motors (refrigerators, pumps, furnace blowers, air conditioners) draw a short surge when they start. Generators are rated for both running (rated) watts and starting (surge) watts.

Total running watts = Σ running watts of everything on at once
Total starting watts = total running watts + the single highest starting watts

Only the largest surge is added because motors rarely start at exactly the same moment. Your generator needs both a running rating ≥ the total running watts and a starting rating ≥ the total starting watts.

Worked example (Briggs & Stratton worksheet)

ItemRunning WStarting W
Refrigerator/freezer5501,350
Furnace fan blower 1/2 HP8002,350
Sump pump 1/2 HP1,2003,000
Plasma TV 50"5000
Lights (6 × 75 W)4500
Total3,500highest: 3,000

Starting watts = 3,500 + 3,000 = 6,500 W. You need a generator with at least 3,500 running watts and 6,500 starting watts.

Assumptions and limits

Common questions

What size generator do I need to run a house?

Add the running watts of everything you need at once, then add the single highest starting wattage. A typical essentials list (fridge, furnace blower, sump pump, TV, lights) comes to about 3,500 running and 6,500 starting watts.

What is the difference between running and starting watts?

Running watts are the continuous power an appliance uses. Starting watts are the brief extra surge a motor needs to start. Generators list both ratings.

Can a generator run a central air conditioner?

It needs a large one. The Briggs & Stratton worksheet lists 3,800 running / 4,950 starting watts for a 24,000 BTU central AC and 6,000 / 6,700 for a 40,000 BTU unit, on top of your other loads.

How much generator do I need for a well pump?

Briggs & Stratton lists a 1/3 HP well pump at 575 running and 1,440 starting watts. Deeper wells use larger pumps, so check your pump nameplate or manual.

Sources

  1. Generac: What Size Generator Do I Need?
  2. Briggs & Stratton: Wattage Worksheet
  3. Champion Power Equipment: Generator Wattage Chart